Permit Number: TC-COM-0524-00993
Parcel: 11618348C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-00993
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/14/2024 Commercial Building APPROVED
06/12/2024 Commercial Electrical APPROVED
06/13/2024 Commercial Mechanical APPROVED
06/05/2024 Site Zoning APPROVED
06/06/2024 Site Engineering NOT REQUIRED
06/14/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/13/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Verify the orientation of the suite. The strip mall is located south of Saint Marys Road with the front entrances located on the north face of the building.
2. Southwest Gas, the local gas utility, provides natural gas at 7” WG, 2 PSIG, and 5 PSIG. The specified ovens require natural gas delivery from 6” to 14” WG. Contact Southwest Gas to determine if a 2 PSIG gas meter will be required. Reference: Section 402.1, IFGC 2018.
06/13/2024 Water - PDSD REQUIRES RESUBMIT Show the location of the utility water meter and the reduced pressure backflow prevention assembly on a site plan. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf
05/30/2024 Fire New Construction REVIEW COMPLETED
05/28/2024 PDSD Application Completeness Express REVIEW COMPLETED