Permit Number: TC-COM-0524-00983
Parcel: 128010040

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0524-00983
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2026 Commercial Building Standard APPROVED Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 10/28/2026
10/28/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Approved with Comments
Date Completed: 10/22/2026
1.E0.4 LIGHTING COMPLIANCE CERTIFICATE/Missing Tucson outdoor lighting calculation:Tucson also has its own
local outdoor lighting calculation that should have been submitted for exterior lighting for determining light pollution.
The calculation has large allowances for full cutoff fixtures and since all outdoor lights are under a canopy that does
provides full cut off, the calculation requirement is waived. However, should the fixtures be installed in such a way as
to negate the full cut off ability of the canopy, the required compliance shall rest upon the Engineer of Record and the
electrical contractor.
2.E4.1 ELECTRICAL ONE-LINE DIAGRAM/Missing Keyed Note 6:Could not locate Keyed Note #6. If not is not used,
no resubmittal is required (Not all notes used?). If new equipment is missing along with Keyed Note #6, a resubmittal
is required.
10/28/2026 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 10/21/2026
10/28/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 10/28/2026
11/05/2026 Water - PDSD Standard APPROVED
10/26/2026 Design Review Standard NOT REQUIRED Property not in a Special District.
10/21/2026 Site Engineering Standard NOT REQUIRED
11/06/2026 Site Zoning Standard NOT REQUIRED
11/12/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/21/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review, please contact CDRC@tucsonaz.gov

The project address on this permit application does not match the project address on the plans submitted (UNIT 110 missing from your the plans submitted). Please update the plans and resubmit, or, submit a Request Change of Address if the permit application is incorrect.

How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
11/04/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0524-00983 (5950 E BROADWAY BL Unit:UNIT 110 TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The addition of lighting fixtures ‘G’ and ‘F’ require compliance with the Outdoor Lighting Code for the site, parcel 128010040. This will require an inventory and lumen calculation for all the exiting and proposed new outdoor lighting on the parcel 128010040.
2. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
3. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different outdoor light sources on your lighting plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
4. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
5. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
6. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
7. Show lamps with a maximum of 3500K color temperature, OLC 402.1. >>> Fixture ‘G’ spec sheet shows a color temperature of 4000K RGBW, which is not compliant.
8. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
9. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

10. Specify any exceptions used.

11. Provide Curfew lighting controls If applicable Per section 403.
11/12/2026 Fire New Construction Standard REVIEW COMPLETED
10/21/2026 PDSD Application Completeness Express REVIEW COMPLETED