Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0524-00963
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2024 | Water - PDSD | APPROVED | |||
| 06/17/2024 | Site Engineering | NOT REQUIRED | |||
| 06/25/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/12/2024 | Design Review | REQUIRES RESUBMIT | The plans indicate development will be mixed-use with Office and Assembly uses proposed. The project is located in the IID, the Rio Nuevo Area, and adjacent to a historic zone. Proposed improvements are visible from the right-of-way. Design review under the standards of the Rio Nuevo Area will be required per UDC 5.12.7. An outline of the RNA review process can be found in UDC 5.12.7.F. Your next step is a pre-application conference with PDSD staff to determine whether the application meets the design standards and requirements of the RNA. More information on submittal requirements and the process for IID/RNA applications can be found at the PDSD Web Page at the following link: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Special-Districts |
||
| 06/06/2024 | External Reviewers - Willdan | REQUIRES RESUBMIT | Willdan Review by: Kenton Steiner, P.E., S.E. Ksteiner@Willdan.com, 480-431-3152 Review Base on 2018 IBC and City of Tucson Amendments unless noted otherwise. Please respond to all comments in writing. 1. G2.0 1006, 1006.2 Recheck you have 2 exits from courtyard space per these sections. Occupant load is greater than 50. 2. Site Plan 1104,1105.1 Please identify the accessible route per 1104 and the accessible entrances per 1105. 3. G2.0 1017.2 Please recheck exit distance includes distance along exit access stairs from second floor. 4. Chapter 13 Please address energy code requirements for new work. 5. 1704 Please submit a completed special inspection form for the project. Russ Healey MEP rhealey@willdan.com 1. Sheet M3.0 - Provide type of refrigerant and pounds of refrigerant in the total system. Provide refrigerant volume (include the piping volume) in the smallest space for a rupture or full loss of refrigerant charge in accordance IMC 1104.4.1 Non-communicating Spaces. 2. Sheet m3.0 - Provide a calculation outside air for Activity Room 1, 2, 3. For Activity 3 comply with IEBC808.2 Altered existing systems. In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured, or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person; or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1. 3. Sheet e3.1 - Provide lighting above each Fan Coil Unit. NEC 210.70 Lighting Outlets Required.(3) Storage or Equipment Spaces. 4. Sheet e4.1 - Provide fault current calculations for HVAC (HP-1) NEC 110.9, 110.10 & 440.4(B). |
||
| 05/26/2024 | Fire New Construction | REQUIRES RESUBMIT | -Indicate in the code analysis if the building has a fire alarm. -Provide OL for each story. If the second story OL >100, a fire alarm is required per IFC 907.2.2 #2. -The code analysis states it is a B-occupancy however it appears to be a mixed occupancy Business/Assembly. Explain why it is only a B-occupancy per IBC/IFC definitions. Also, an assembly occupancy could require fire sprinklers per IFC 903.2.1 john.vincent@tucsonaz.gov 5203495581 |
||
| 06/21/2024 | Historic | REQUIRES RESUBMIT | Property is a contributing building to the Armory Park National Register Historic District but outside of the locally listed Historic Preservation Zone. The proposed exterior work (front facade and courtyard) requires review by PRS. Please provide documentation noted under Full review in the Historic and Special Districts application instructions packet (https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf). Once assembled, please submit the information under the Historic sub-record. Questions? Jodie.Brown@tucsonaz.gov | ||
| 06/12/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0524-00963 130 S SCOTT AV. – OCR-2 Remodel existing Tucson Children's Museum w/ Exterior ADA Ramp addition (1st Review) TRANSMITTAL: June 12, 2024 COMMENT: Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in OCR-2 zone (UDC 4.7.27). 1. As this site is located with in the downtown core and Rio Nuevo Area (RNA) Historic review and Design Review is required and must be approved prior to approval of this plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 05/21/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 06/25/2024 | ROW Engineering Review | REVIEW COMPLETED | ROW permit required prior to working in the ROW |