Permit Number: TC-COM-0524-00952
Parcel: 117121940

Address:
72 E CONGRESS ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00952
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2024 Water - PDSD APPROVED
06/21/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/21/2024 Design Review REQUIRES RESUBMIT The proposal shows modifications to the previous Design Package approved in 2019 under Activity # T19SA00270. Please submit a revised Design Package demonstrating compliance with Rio Nuevo Area (RNA) overlay and historic preservation standards. The Design Package needs to be submitted as a subrecord of TC-COM-0524-00952, and needs to include the materials specified here:
https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf
Please also include as part of the Design Package a letter from the property owner authorizing you to process the new Design Package.
If you could please send me an email to maria.gayosso@tucsonaz.gov when you submit the new Design Package, it would be very much appreciated. Please email me if you have any questions. Thank you.
05/30/2024 External Reviewers - Willdan REQUIRES RESUBMIT For question regarding review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments will be followed with the initials (BM)
1. Sheet a0.1 Plan notes identify existing type of construction as VB. Fire resistance rating requirements note on plan identifies type III-B. Clarify per 2018 IBC 107.2.1
2. Sheet a0.1 Elevator shop drawings are not noted to be deferred or part of TI permits. Clarify 2018 IBC 107.2.1 & 107.3.4.1 (BM)
3. Sheet a3.0 Key note 315 for stairs identifies details, will need to provide typical details on plans for guards, handrails, handrail terminations and dimensions to comply with 2018 IBC sections 1014 & 1015. (BM) Did not identify in plans
4. Sheet a3.0 Structural step details refer to architectural for dimensions / information. Will need to provide riser and tread information on plans for review for all stir sections to comply with 2018 IBC 1011.5 (BM)
5. Sheet a3.1 Demo plan keynote 208 identifies door as existing and to remain. Key note 303 identifies a new door. New door 100a will need to meet minimum opening width of door leaf of 32" per 2018 IBC 101.1.1 (BM)
6. Sheet a3.2 Provide detail and dimensions for guard and handrails at elevated walkway as per note key note 322 for review to comply with 2018 IBC 1015 (BM)
7. Sheet a4.0 RCP key note #5 identifies 1HR horizontal assembly for ceiling area below stair enclosure. Provide detail , assembly type for review for connection to vertical wall assembly to maintain 1 HR separation. 2018 IBC 107.2.1 (BM)
8. Sheet P3.1 Plumbing fixture schedule identifies 24 FU for water closets, pump calculation identifies 17 FU current demand. Clarify per 2018 IPC 712.3.1 (BM)
06/21/2024 Historic REQUIRES RESUBMIT Due to the proposed modifications, the project should be reviewed by Historic for a Minor review through the Rio Nuevo Area (RNA) review process. Please cloud the areas of change. Please provide clips of what was originally approved. Once assembled, please submit under the building permit sub-record. Questions? Jodie.Brown@tucsonaz.gov
06/17/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
06/11/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review

PROJECT: TC-COM-0524-00952
72 E CONGRESS ST. – OCR-2
Shell work (1st Review)

TRANSMITTAL: June 11, 2024

COMMENT: Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in OCR-2 zone (UDC 4.7.27).

1. As this site is located with in the downtown core and Rio Nuevo Area (RNA) Historic review and Design Review is required and must be approved prior to approval of this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/09/2024 Fire New Construction REVIEW COMPLETED
05/20/2024 PDSD Application Completeness REVIEW COMPLETED