Permit Number: TC-COM-0524-00948
Parcel: 12404003C

Address:
1420 E 1ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0524-00948
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2024 Site Zoning APPROVED
06/20/2024 Water - PDSD APPROVED
06/17/2024 Site Engineering NOT REQUIRED
06/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/06/2024 External Reviewers - Stantec REQUIRES RESUBMIT May 31, 2024
1st Review

Dean Alan Architects, PLLC
Attn: Angela Gee
5151 E. Broadway Blvd. Suite 1050
Tucson, Arizona 85711

Re: CHI OMEGA BASEMENT
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0524-00948
Stantec Project Number: 185215066
Stantec File Number: TUC-24-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-3 V-B 2,898 9 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate on the cover page that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).


Sheet T1

1. Please review the occupancy groups listed. The Group R1 listed does not fit the use provided. Group R1 Occupancies are classified as sleeping units where occupants are transient in nature (i.e. hotels/motels). This use would classify as a Group R2 or Group R3 depending on the occupant load. Please provide the occupant load for the building to clarify Group R2 or R3 classification and revise accordingly. [Ref. IBC 2018 Sec. 310]

Sheet A1.3

1. The Occupant Load indicated only includes the Residential net area. The other rooms are not included in the calculation. The factor used for the residential areas also needs to be revised for assembly unconcentrated (tables and chairs) at a factor of 15 net. Please provide a complete occupant load breakdown of all rooms and spaces in the basement along with the updated occupant load factor for the study area and craft room.

2. The First Floor Plan staircase at the lobby does not look right. It does not appear to depict a clear path to the exit discharge from the basement. Please clarify the design so a complete means of egress is depicted from the basement floor using this exit.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P1.2

1. Please provide updated water pressure calculations. [Ref. IPC 2018 Sec. 603]

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/26/2024 Fire New Construction REQUIRES RESUBMIT -Sheet T1, development data, states occupancy type as R1/R3. I believe this is an R2 Sorority house per IFC definition of Residential Group R2.
john.vincent@tucsonaz.gov
5203495581
05/20/2024 PDSD Application Completeness Express REVIEW COMPLETED