Permit Number: TC-COM-0524-00934
Parcel: 11709123A

Address:
246 W 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0524-00934
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/29/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The previous electrical comments are not addressed completely.

A; ” Provide updated Plans/calculations”.

B; “2. Provide a complete line diagram detailing the equipment to be replaced”

1 The Site plan does not show the locations of the existing and new sub-panels.

2 The line diagram is not complete and is a hand drawn sketch (Possibly the existing equipment) with no information of the new equipment. (Not an ‘All-in-One Meter/Panel Combo) as stated per the note next to the diagram.

2a Show the ratings of all the new or replaced equipment. Voltage, Amps, Phase, AIC, all conduit, conductor sizes, types and quantities, including the service secondary's.

2b Provide load calculations that correlate with complete panel schedules.

3 See the City of Tucson Commercial Plan/Permit Submittal Requirements for additional information; https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/commercial-permits/commercial_submittal_requirements_january2023-1.pdf

Be advised that due to the nature of the submitted documents and plan review comments, additional review comments may be generated per the subsequent plan review. It would be advisable to obtain the services of an electrical design professional, an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan/Permit Submittal Requirements.
07/29/2024 PDSD Application Completeness Express REVIEW COMPLETED