Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0524-00929
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/20/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0524-00929 (4750 S PARK AV TUCSON, AZ 85714) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Is this service equipment (Main Breaker) and what is the voltage and amperage, phase? We need all the specs of the equipment that this part is installed in. 2. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. 3. If you plan to repair the part then it must be re-certified, by an independent testing agency, per its original listing, NEC 110.3(A)-(C). See also NEC 110.21(A)(2) for additional marking requirements. You will need to provide the re-certification certificate prior to final inspections. 4. Or you can replace the part with the same part (like-for-like). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |