Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0524-00927
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/18/2024 | Commercial Electrical | APPROVED | |||
06/18/2024 | Commercial Mechanical | APPROVED | |||
06/18/2024 | Commercial Plumbing | APPROVED | |||
06/07/2024 | Site Zoning | APPROVED | |||
06/18/2024 | Water - PDSD | APPROVED | |||
06/12/2024 | Site Engineering | NOT REQUIRED | |||
06/20/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/20/2024 | Commercial Structural | REQUIRES RESUBMIT | Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed. 1. Pleas amend plans to show compliance with IEBC 305.7 that requires accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7. A. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made. 2. Please amend plans to address the fire alarm requirements of IBC 907.2, where fire alarms are required for B occupancies with greater than 100 occupants above the lowest level of discharge. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
05/26/2024 | Fire New Construction | REQUIRES RESUBMIT | -Indicate in the code analysis if the building has a fire alarm. Per IFC 907.2.2, a fire alarm is required in this building since the OL of the second floor is > 100. john.vincent@tucsonaz.gov 5203495581 |
||