Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0524-00926
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/10/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/10/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical Plan review comments and provide a written response. 1 REF; Insta-hot Water Heater ‘WH1’. The new Insta-hot water heater shown on the plumbing plan schedule ‘WH1; calls out for the electrical requirements at 29A /120V/ 1 phase. The electrical floor plan shows a 30A/1P disconnect. The panel schedules do not identify ‘WH1’. And the Amp and phase of the 2 water heaters shown in the panel schedules do not correlate. Please clarify, and identify the Circuiting and panel designation for all electrical circuits shown in the electrical floor plans. REF;2018 IBC section 107.2.1, 2017 NEC 408.4. |
||
12/06/2024 | PDSD Application Completeness | REVIEW COMPLETED |