Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/10/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical Plan review comments and provide a written response.

1 REF; Insta-hot Water Heater ‘WH1’. The new Insta-hot water heater shown on the plumbing plan schedule ‘WH1; calls out for the electrical requirements at 29A /120V/ 1 phase. The electrical floor plan shows a 30A/1P disconnect. The panel schedules do not identify ‘WH1’. And the Amp and phase of the 2 water heaters shown in the panel schedules do not correlate. Please clarify, and identify the Circuiting and panel designation for all electrical circuits shown in the electrical floor plans.

REF;2018 IBC section 107.2.1, 2017 NEC 408.4.