Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-0524-00926
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/25/2024 | Site Engineering | APPROVED | |||
11/25/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/25/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Previous electrical plan review comment; . 1 Please provide electrical for the new instantaneous water heater, load calculations and panel schedule and location. See plumbing plans for specifications. 1 The previous electrical plan review comment was not addressed. See Plumbing plan sheets P1.00 and P2.00 (Detail 201) for information about location and electrical requirements for WH-1 associated with the restroom. 2 Why are there 2 locations shown for the scope of work in the electrical plans? See plan sheet e1.0 (Keyplan). Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
11/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |