Permit Number: TC-COM-0524-00926
Parcel: 116193560

Address:
440 N BONITA AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0524-00926
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2024 Site Engineering APPROVED
11/25/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Previous electrical plan review comment; . 1 Please provide electrical for the new instantaneous water heater, load calculations and panel schedule and location. See plumbing plans for specifications.

1 The previous electrical plan review comment was not addressed. See Plumbing plan sheets P1.00 and P2.00 (Detail 201) for information about location and electrical requirements for WH-1 associated with the restroom.

2 Why are there 2 locations shown for the scope of work in the electrical plans? See plan sheet e1.0 (Keyplan).

Ref; 2018 IBC section 107.2.1, 2017 NEC.
11/12/2024 PDSD Application Completeness REVIEW COMPLETED