Permit Number: TC-COM-0524-00910
Parcel: 13705501Q

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00910
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2024 Commercial Plumbing APPROVED
06/18/2024 Commercial Structural APPROVED
06/07/2024 Site Zoning APPROVED
06/18/2024 Water - PDSD APPROVED
06/18/2024 Commercial Mechanical NOT REQUIRED
06/12/2024 Site Engineering NOT REQUIRED
06/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/17/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide complete panel schedules associated with all the new power and lighting branch circuit requirements. NEC 408.4.

2 Assign device and lighting branch circuits and panel designations and correlate with the panel schedule(s). NEC 408.4.

Ref; 2018 IBC section 107.2.1, 2017 NEC
05/26/2024 Fire New Construction REVIEW COMPLETED
05/16/2024 PDSD Application Completeness REVIEW COMPLETED