Permit Number: TC-COM-0524-00903
Parcel: 11310099A

Address:
2611 N WARREN AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0524-00903
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2024 Commercial Plumbing APPROVED
05/29/2024 Site Zoning APPROVED
05/29/2024 Water - PDSD APPROVED
05/21/2024 Site Engineering NOT REQUIRED
05/29/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/29/2024 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0524-00903
ADDRESS/PARCEL: (2611 N WARREN AV TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Provide detail drawing for Storage Shed: Structures and portions thereof shall be provided with anchorage foundation to resist uplift and sliding forces and lateral forces and wind per IBC 1604.8
(Ground Anchor Screws is an option, ensure you submit the structural engineer's calculation enumerating the type, how many for each container and embedment depth, submit the product info and its specification).
2. Provide detail drawing for the 6 ft high steel fence to include the footing.
3. Door 101A: An exit access shall not pass through a room that can be locked to prevent egress. IBC 1016.2 Please add a note complying to this requirement.
4. Please update your Plumbing Fixture Calculations. You indicate providing 1 WC and 1 Lav. However, you actually have 2 WC and 2 Lavs
5. Service Sink: Where occupant load is 15 or less, a service sink is not required. Please provide a service sink since you have 48 occupants.
6. Please resubmit.
05/29/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Ref; Plan sheet E5.0. The panel schedule Branch circuit descriptions is insufficient. Provide as required

Include panel numbers, voltage, phasing, location, bus size, circuit number, breaker sizing, number of poles, A.I.C rating, number of lights and/or receptacles by circuit, total KVA load. NEC art 408.4.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
05/29/2024 Commercial Mechanical REQUIRES RESUBMIT A return air duct for HP-3 is labeled as a supply air duct in the mechanical plan, 2/M1. (Note there is a duplicate set of mechanical and plumbing drawings in this plan set.)
05/20/2024 Fire New Construction REVIEW COMPLETED
05/14/2024 PDSD Application Completeness Express REVIEW COMPLETED