Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-0524-00878
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/26/2024 | Commercial Electrical | APPROVED | |||
06/27/2024 | Commercial Plumbing | APPROVED | Note: the aerator on the specified lavatory faucet limits the flow to 0.5 gallons per minute. The faucet has a maximum cycle time of 30 seconds which will limit the water delivery to 0.25 gallons per cycle (not 0.25 GPM). | ||
06/27/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/27/2024 | Commercial Mechanical | REQUIRES RESUBMIT | The oven specification shows an electrical power requirement of 12.6 kW – where is this included in the cooling load calculation? [Initial comment: Verify that the proposed HVAC system is able to accommodate the thermal load of the conveyor oven or install a Type II hood over the oven. Reference: Sections 507.1, 507.2, and 507.3, IMC 2018.] | ||
06/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |