Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/11/2024 Commercial Mechanical REQUIRES RESUBMIT The total miscellaneous internal cooling loads shown for the two existing rooftop units is 22,452 BTUH. An oven drawing 12.6 kW will produce a cooling load of 42,992 BTUH. How is the additional internal cooling load handled? [Second comment: The oven specification shows an electrical power requirement of 12.6 kW – where is this included in the cooling load calculation?] [Initial comment: Verify that the proposed HVAC system is able to accommodate the thermal load of the conveyor oven or install a Type II hood over the oven. Reference: Sections 507.1, 507.2, and 507.3, IMC 2018.]