Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0524-00877
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/10/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0524-00877 (3532 S BELMAR AV TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Show the mast height on the electrical riser diagram and show the overhead electrical line over the driveway is compliant per NEC 230.24. a. Provide 10’ clearance above pedestrian accessible areas, 2017 NEC 230.24(B)(1) b. Provide 12’ clearance above residential property and driveways (Voltage under 300v), 2017 NEC 230.24(B)(2) 2. Clarify the scope of work. The permit details state this is a 100A upgrade while the provided plans show a 200A upgrade. |
||