Permit Number: TC-COM-0524-00872
Parcel: 13609014B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0524-00872
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2024 Water - PDSD APPROVED
08/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/06/2024 Commercial Plumbing REQUIRES RESUBMIT Coordinate detail 5/P3.0 with the installation instructions for the specified lavatory faucet. Reference: Section 303.2, IPC 2018. [Initial comment: Verify that the specified sensor faucets for the restroom lavatories have an automatic time-out so that they will dispense a maximum of 0.25 gallons per metering cycle (e.g. 0.5 GPM for 10 to 30 seconds). Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. ]
07/02/2024 PDSD Application Completeness Express REVIEW COMPLETED