Permit Number: TC-COM-0524-00795
Parcel: 13705565D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00795
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2024 Site Zoning APPROVED
06/10/2024 Water - PDSD APPROVED
06/05/2024 Site Engineering NOT REQUIRED
06/10/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
05/17/2024 External Reviewers - Willdan REQUIRES RESUBMIT Sheet Cover Sheet; For questions regarding Plan Review comments please contact: Dino M. Accardo, MCP, CBO, E: daccardo@willdan.com. Fire Plan Review is NOT within the scope of this review. All applicable comments will be followed with the initials, DMA.
1. Sheet a0.1; Exhaust Hoods are included with plans, clarify intent of listing as separate submittal. If intent is to proceed and include in this review, provide all equipment in kitchen and specs. DMA
2. Sheet a0.1, 2018 IBC Ch 5; Building is existing, however the existing building data is still required for height and area. DMA
3. Sheet a0.2, 2018 IBC [A]107.2.6 Site plan. The construction documents submitted with the application for permit shall be accompanied by a site plan showing to scale the size and location of new construction and existing structures on the site, distances from lot lines; and it shall be drawn in accordance with an accurate boundary line survey. Also see Table 602 for fire separation distance requirements. DMA
4. Sheet A0.2, 2018 IBC 1028.1 General. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide a direct path of egress travel to grade. The exit discharge shall not reenter a building. The combined use of Exceptions 1 and 2 shall not exceed 50 percent of the number and minimum width or required capacity of the required exits. The two exterior exits from the outdoor dining are still within the exit access portion of the means of egress. In order to comply with remote 2nd means of egress requirements Door 100c must be factored in. DMA
5. Sheet A0.2, 2009 A117.1 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Door schedule shows gates 100b and 100c is gate that self closes. Provide a minimum of 12 inches as shown in Fig b. DMA
6. 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Provide proper door maneuvering clearance at bath door 117a. DMA
7. Sheet a0.2, 2018 IPC 405.3.2 Public lavatories. In employee and public toilet rooms, the required lavatory shall be located in the same room as the required water closet. DMA
8. Sheet a5.1, 2018 IBC 1010.1.10 Panic and fire exit hardware. Swinging doors serving an occupant load of 50 or more in a Group A occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Gates 100b and 100c. NOTE: 1010.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. DMA
9. Sheet P1.3, 2018 IFGC and 2018 IPC; As required for review and to verify compliance with several applicable codes, provide either a scaled gas and drainage isometric or can be dimensioned to determine developed lengths. DMA
10. Sheet P3.2, 2018 IPC 1003.3 Grease interceptors. Grease interceptors shall comply with the requirements of Sections 1003.3.1 through 1003.3.8. Provide grease interceptor as required in this section. Include specifications and sizing calculations. DMA
11. Sheet E2.0, 2017 NEC 210.8; Provide GFCI protected receptacles in all locations as listed in this section. DMA
05/26/2024 Fire New Construction REQUIRES RESUBMIT -Sheet A0.2 shows an exit sign over the drink station however this sign is not shown on the electrical sheets. Remove this exit sign and modify exit plan. An exit from the dining room cannot pass through a kitchen. IFC 1016 #5.
-Indicate if bulk CO2 for beverage dispensing will be used and location of CO2 container/dewar. If bulk CO2 >100 lbs, CO2 alarm is required per IFC 5307.3.2.
-Resolve all building comments.
john.vincent@tucsonaz.gov
5203495581
05/08/2024 PDSD Application Completeness REVIEW COMPLETED