Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00792
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2024 Commercial Mechanical APPROVED
06/10/2024 Commercial Plumbing APPROVED
06/11/2024 Commercial Structural APPROVED
06/03/2024 Site Zoning APPROVED
06/10/2024 Water - PDSD APPROVED
06/04/2024 Site Engineering NOT REQUIRED
06/11/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/06/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The panel schedule branch circuit descriptions must be more accurate. Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include an approved degree of detail that allows each circuit to be distinguished from all others. NEC art 408.4.

2 Provide Tamper Resistant Receptacle for all replacements. NEC arts 406.12 and 210.

3 Install Combination AFCI protection for protection of branch circuits as applicable per NEC art 210.12.

4 Lamp output color temperature for the replaced exterior luminaires shall not exceed 3500K. OLC section 402.1.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code (OLC).
05/13/2024 Fire New Construction REVIEW COMPLETED
05/08/2024 PDSD Application Completeness REVIEW COMPLETED