Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0524-00789
Parcel: 12501123A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0524-00789
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2024 Commercial Mechanical APPROVED
05/10/2024 Site Zoning APPROVED Zoning is approving the tenant improvement, however, please provide an ADA-compliant path from the ADA parking spaces to the north entrance.
06/04/2024 Site Engineering NOT REQUIRED
06/11/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/05/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide full compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior patio lighting.

Ref; 2012 City of Tucson Outdoor Lighting Code.
06/10/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
2. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g. 24” for ½” supply pipe).
4. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1 and 2902.5, IBC 2018 and Section 410.3, IPC 2018. Show the location of the drinking fountains on the plumbing sheets and if they are new, provide their specifications.
06/11/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Sheet G-111: Please amend plan so all IBC code references are referring to the 2018 edition. IBC 107.2.1 For example, Sheet G-111 Exiting plan and Sheet A-700 ….are showing 2012, 2015 IBC. Please treat this as a typical note. See bubbled areas on plans.
2. Sheet A-111: Please amend plans to show how the accessibility elements have been upgraded. IEBC 305.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are not fully compliant, upgrades shall be required in accordance with IEBC.305.7. For example, Restroom A does not appear to be fully compliant with the 2009 ICC A117.1 604.3 clearances around the water closet.

A. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made.
3. Sheet A-401: Please amend plans to show the clearance width around the water closet as 60 inches wide and 56 inches deep as required by 2009 ICC A117.1 604.3. & 604.3.2

Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/10/2024 Water - PDSD REQUIRES RESUBMIT Provide the size and location of both the water service meter and the associated reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2018.
05/26/2024 Fire New Construction REVIEW COMPLETED
05/08/2024 PDSD Application Completeness REVIEW COMPLETED