Permit Number: TC-COM-0524-00789
Parcel: 12501123A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0524-00789
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2024 Commercial Electrical APPROVED
07/29/2024 Commercial Structural APPROVED
07/29/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/25/2024 Commercial Plumbing REQUIRES RESUBMIT Show how the proposed hot water recirculation system on the First Level Plumbing Plan serves both lavatories. Reroute the hot water return for the recirculating hot water system to connect to the cold water inlet of the water heater. Note: An ASSE 1070 temperature control device is designed for point-of-use applications while an ASSE 1017 is typically used as a master mixing valve located at the hot water source, as shown in detail 4/P-111. Reference: Section 607.2.2, IPC 2018 and Section 107.2.1, IBC2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g. 24” for ½” supply pipe).]
07/25/2024 Water - PDSD REQUIRES RESUBMIT Keynote 8, P-111, states that the backflow assembly is located in a pit with a 1-1/4” water meter. A reduced pressure backflow assembly is not allowed to be installed in a pit but must be at least 12” above grade. For installation of reduced pressure backflow assembly instructions, see Tucson Water Standard Detail SD 1802. https://www.tucsonaz.gov/files/sharedassets/public/v/1/living-and-working/parks-and-recreation/documents/sd-1802.pdf
Verify the size of the water meter: Tucson Water does not offer a 1-1/4” water meter. [Initial comment: Provide the size and location of both the water service meter and the associated reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2018.]
06/21/2024 PDSD Application Completeness REVIEW COMPLETED