Review Date Reviewer's Name Type of Review Description Status Comments
06/25/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/25/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
2. Provide a site plan that clearly shows the location of the HVAC unit to be replaced. Reference: Section 107.2.1, IBC 2018.