Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0524-00766
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2024 | Commercial Mechanical | APPROVED | |||
| 11/07/2024 | Commercial Structural | APPROVED | |||
| 11/19/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/12/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please provide a complete grounding detail for the new Electrical Service. 2 The Electrical Site Plan ‘NOTE’ states, “NO SITE LIGHTING ON THIS PROJECT”. Why are there exterior Outdoor Lighting Code lumen calculations in the plan? Any exterior lighting should be included as site lighting. Also, the lighting area is incorrect. Should be lighting area ‘E3’ not ‘E3a’. 3 Provide a complete luminaire schedule that also correlates with the Outdoor Lighting calculations. 4 Please indicate Voltage, Phase, and Amp rating for the New Electrical Service. Including AIC and fuse Types for the Main Service Disconnects. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements. |
||
| 11/19/2024 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review PROJECT: TC-COM-0524-00766 3102 East 22nd Street – C-1 Change of use from retail to Food Service (2nd Review) TRANSMITTAL DATE: November 19, 2024 Please resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed. 1. Zoning acknowledges that development package TD-DEV-0824-00229 has been submitted for the proposed change of use and site improvements. As TD-DEV-0824-00229 has not completed its first full review, Zoning cannot accurately compare the building plans with the building footprint, gross floor area, and height shown on TD-DEV-0824-00229. Zoning cannot approve TC-COM-0524-00766 until the development package has been approved by all reviewers. 2. If any of the development package civil plans are to be submitted with the building plans, the civil plans should either be marked "reference only" or be the stamped development package plans. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 11/04/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 10/28/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |