Permit Number: TC-COM-0523-01409
Parcel: 13624228D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-0523-01409
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written rsponse.

The house panel schedule in not complete. Provide a complete house panel. Indicate the amp rating on the panel schedule and show the OCPD protecting the feeder and EV panel. NEC 408.4. See previous review comments.

Why is EV-5 clouded in red along with the ‘GW’ on the site plan? This was not in the previous site plan. Please clarify.

The Building #3, House panel, and “DP1” Are not identified on the Site plan. Please identify.

Ref 2018 IBC section 107.2.1, 2017 NEC.
07/12/2023 PDSD Application Completeness Express REVIEW COMPLETED