| 07/13/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written rsponse. The house panel schedule in not complete. Provide a complete house panel. Indicate the amp rating on the panel schedule and show the OCPD protecting the feeder and EV panel. NEC 408.4. See previous review comments. Why is EV-5 clouded in red along with the ‘GW’ on the site plan? This was not in the previous site plan. Please clarify. The Building #3, House panel, and “DP1” Are not identified on the Site plan. Please identify. Ref 2018 IBC section 107.2.1, 2017 NEC. |
||