Permit Number: TC-COM-0523-01408
Parcel: 13711428V

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0523-01408
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1. Ref; Electrical Line Diagram.

(a) The Line Diagram shows the EV Charging Stations and GW connected to existing ‘HP’. Is this the same Panel shown on as ‘MS PNL-1'? Please clarify and coordinate panel identifications to correlate with each other.

(b) The Conduit Specifications table shows 3-#8AWG conductors in ½ inch conduit. The conduit is undersized. Please revise to ¾ inch. See NEC Table C.11.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
06/29/2023 PDSD Application Completeness Express REVIEW COMPLETED