| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/10/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. Ref; Electrical Line Diagram. (a) The Line Diagram shows the EV Charging Stations and GW connected to existing ‘HP’. Is this the same Panel shown on as ‘MS PNL-1'? Please clarify and coordinate panel identifications to correlate with each other. (b) The Conduit Specifications table shows 3-#8AWG conductors in ½ inch conduit. The conduit is undersized. Please revise to ¾ inch. See NEC Table C.11. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||