Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.6
Permit Number - TC-COM-0523-01406
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.6
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/19/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The panel identifications still do not correlate with each other. See the previous plan review comment. The sub-Panel feeding the EV Chargers is identified as the 'Main Service Panel' The Main Service Panel would be the 800 amp Panel by NEC code definition. Please label the panels correctly. 2018 IBC section 107.2.1, 2017 NEC |
||
| 07/14/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |