Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0523-01406
Parcel: 134264130

Address:
818 S LANGLEY AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.6

Permit Number - TC-COM-0523-01406
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/19/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
The panel identifications still do not correlate with each other. See the previous plan review comment. The sub-Panel feeding the EV Chargers is identified as the 'Main Service Panel' The Main Service Panel would be the 800 amp Panel by NEC code definition. Please label the panels correctly.
2018 IBC section 107.2.1, 2017 NEC
07/14/2023 PDSD Application Completeness Express REVIEW COMPLETED