Permit Number: TC-COM-0523-01405
Parcel: 14043013F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01405
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2023 Site Zoning APPROVED
06/30/2023 Water - PDSD APPROVED
06/15/2023 Site Engineering NOT REQUIRED
06/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/13/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0523-01405


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/13/2023 2:03:19 PM


Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 6/13/2023 2:02:26 PM
1. Sheet C2: The occupancy classification listed is incorrect. The International Building Code does not recognize a B1 or B2 occupancy classification. Provide an accurate occupancy classification in accordance with Chapter 3 of IBC.
2. Sheet A2.1: The women's accessible stall is located in the clear floor space for the restroom door. Provide clear floor space for the restroom door in accordance with the 2010 ADA.


Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/13/2023 2:05:13 PM


Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/13/2023 2:03:09 PM


Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/13/2023 2:05:19 PM
06/05/2023 Fire New Construction REVIEW COMPLETED
06/01/2023 PDSD Application Completeness Express REVIEW COMPLETED