Permit Number: TC-COM-0523-01393
Parcel: 117042390

Address:
537 N 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01393
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/05/2023 Commercial Building REQUIRES RESUBMIT Please respond to the following: 1.) IBC 705 Exterior Wall Projections - Not less than 1 hour fire-resistance-rated construction to within 5 feet of line used to determine the fire separation distance. 2.) Per IBC 601 & 602 based on the occupancy group M for Mercantile use and if you have construction type IIB or VB, a minimum 10 ft fire separation distance is required to have no fire-resistance rating on the exterior walls of the structures. 3.) Please show the structures on the drawing to graphically see their locations relative to the property lines 4.) Fire separation based on occupancy shall be required per IBC Table 508.4 (you have the condition where property line bisects through the existing structure). 5.) Comply to IBC section 716. Openings such as windows near the property line(s) are to meet the fire protection, temperature & hose streaming requirements. Opening allowable area based on the Fire Separation Distance per IBC Table 705.8. Existing openings: May we suggest a floor plan be included in this submission to address locations of openings to include the neighboring structures.. Please resubmit.
06/14/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0523-01393
537 N 6TH AV Zoning C-3

TRANSMITTAL DATE:‎June 14, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: As you are proposing multiple uses a Development package will be required, A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at : https://tdc-online.tucsonaz.gov/#/The DP will need to be approved prior to approval of this building permit.



If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
05/31/2023 Fire New Construction REVIEW COMPLETED
05/30/2023 PDSD Application Completeness Express REVIEW COMPLETED