Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0523-01384
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2024 | Water Sterilization Report (Deferred Submittal) Express | APPROVED | |||
| 03/14/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/14/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | Based on the air balance technician’s notes, it is not known if the building will provide the requisite ventilation or that the any of the six Type I and Type II hoods will pass the required capture and containment test. Reference: Sections 403.1, 507.6, and 508.1.2, IMC 2018. | ||
| 03/13/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |