Permit Number: TC-COM-0523-01384
Parcel: 128010210

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0523-01384
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2024 Water Sterilization Report (Deferred Submittal) Express APPROVED
03/14/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/14/2024 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Based on the air balance technician’s notes, it is not known if the building will provide the requisite ventilation or that the any of the six Type I and Type II hoods will pass the required capture and containment test. Reference: Sections 403.1, 507.6, and 508.1.2, IMC 2018.
03/13/2024 PDSD Application Completeness Express REVIEW COMPLETED