Permit Number: TC-COM-0523-01374
Parcel: 133231420

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01374
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2023 Site Zoning APPROVED
06/08/2023 Site Engineering NOT REQUIRED
07/24/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/26/2023 Water - PDSD REQUIRES RESUBMIT Show the location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1 and 107.2.6, IBC 2018
07/24/2023 External Reviewers - Stantec REVIEW COMPLETED
05/31/2023 Fire New Construction REVIEW COMPLETED
05/25/2023 PDSD Application Completeness REVIEW COMPLETED