Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.4

Permit Number - TC-COM-0523-01374
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
04/04/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The contractor has increased the outside air to the salon space, bringing the outside air up to 72% of the design airflow, but this is not a balancing issue: The ventilation design criteria are incorrect. The architect needs to redesign the HVAC system to provide the required ventilation per Table 403.3.1.1, IMC 2018. The requirement calls for significantly more outside airflow and exhaust, but also footnote b states that recirculation of air from such spaces cannot be recirculated to other occupancies. Reference: Section 403.2.1(3), IMC 2018. [Initial comment: The ventilation requirement for beauty salons per Table 403.3.1.1, IMC 2018, requires 20 CFM of outside air per person, 0.12 CFM per square foot of salon area, and 0.6 CFM per square foot of exhaust for the salon. The design of the salon ventilation does not comply with the code requirements.]