Permit Number: TC-COM-0523-01374
Parcel: 133231420

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01374
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/06/2024 External Reviewers - Stantec REQUIRES RESUBMIT June 6, 2024
1st Review

American Design Consulting, INC
Attn: Rhonda Rawson, RA
P.O. Box 13152
Tucson, Arizona 85732

Re: GB STUDIO
TENANT IMPROVEMENT - REVISIONS

City of Tucson Permit Number: TC-COM-0523-01374
Stantec Project Number: 185215066
Stantec File Number: TUC-24-039

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 3,934 45 Yes Yes
Separate Permits: Fire Sprinklers and fire alarms.
Deferred Submittals: N/A
Special Inspections: N/A

MECHANICAL COMMENTS

Sheet M-1.0

1. Per 2018 IMC Table 403.3.1.1 the outside air to be provided for a beauty salon is 20 CFM per person, and not 7.5 CFM per person. This adjusts the calculation of required outdoor air from 810 CFM to 1,372 CFM.
a. 45 persons x 20 CFM per person equals 900 CFM
b. 0.12 CFM per s.f. x 3,934 s.f. equals 472 CFM
c. Total outdoor air required is 1,372 CFM
The 2 air handlers are providing a total of only 1,200 CFM of outdoor air (600 CFM per air handler). The outdoor air falls 172 CFM short of the required outdoor CFM.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415