Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Permit Number - TC-COM-0523-01374
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/08/2024 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The ventilation requirement for beauty salons per Table 403.3.1.1, IMC 2018, requires 20 CFM of outside air per person, 0.12 CFM per square foot of salon area, and 0.6 CFM per square foot of exhaust for the salon. The design of the salon ventilation does not comply with the code requirements. | ||