Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01364
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/03/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Janet Matz
jmatz@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/9/2023 7:31:09 AM
no structural work was included with this submittal



Building(B) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 8/1/2023 1:22:26 PM
1. Original Comment: The plans indicate this is to be a warehouse, however the definition of a warehouse is to store goods and raw materials. This does not match the intended use of the space as described on sheet A0.0. Indicate the actual use on the drawings and update all sheets. The definition of a repair garage per IBC is a building used for servicing or repairing motor vehicles which appears to be closer to the actual intended use. Per email conversation on June 29 with the architect, the IBC designation for this space is S-1 not F-1. update the information on the cover sheet to match the intended use.

2. New Comment: Remove the room designations that still indicate "warehouse" on sheets A3.0, A5.0, A6.0 and indicate Car Wrap as shown in the other revised sheets.

3. New Comment: Please bubble all changes on the architectural drawings and indicate the revision number and dates on the title blocks.



Mechanical(M) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 8/1/2023 1:40:06 PM
1. Original Comment: Provide mechanical ventilation in the area in which vehicles will be worked on including a gas detection system in accordance with 2018 IBC 406.8. The only ventilation is shown in the storage room. No gas detection system was found on the drawings. please provide a gas detection system including construction details for its installation on the drawings.

2. New Comment: the plans indicate the required make up air will be through the roll- up doors however the doors are shown to be solid and will not provide the required makeup air per 2018 IMC 501.4. it is not acceptable to assume the
doors will be open at all times that the building is occupied. Clarify how the make up air will be provided and correct the note by removing the "warehouse" designation.

3. New Comment: The new exhaust fan note indicates to split the fan inlet into two hi/low ducts. The only additional details are to terminate one duct below the roof deck. Indicate the locations of the new vent inlets on the drawings, and provide construction details for their installation.



Electrical(E) Reviewer
Janet Matz
jmatz@safebuilt.com
Denied
Reason:
Date Completed : 8/1/2023 1:27:52 PM
1. Original Comment: Update the general notes on sheet E1.0 to match the project. note a indicates to convert a shell building to warehouse and offices.

The general note was updated however the room designation still indicates "warehouse" on sheet E2.0. Indicate Car Wrap as shown in the other revised sheets.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 8/2/2023 9:43:15 PM
Second Plumbing Review:
1. RESOLVED- Clarify if the new space is to only install film or if the cars will be detailed and washed in the space as well. If the work includes discharge of oil, grease, sand, or other substances such as chemicals into the public sewer, a floor drain to an oil separator will be required. 2018 IPC section 1003.1 and 1003.4.,

2. RESOLVED-In addition, can you please correct the distance to the accessible restroom on the drawings? I need the accessible route from the farthest point in the new unit to the actual door to the restroom, not the front door of the other unit. IPC 403.3.1, 403.3. Also provide a note on plan that the operational time of the unit with the restrooms will be the same or exceed the new unit to ensure restrooms will always be accessible.

3. No Response- Will OSHA require an eye wash station for this use? If so It should be shown on the plans.

4). Now that the required interceptor/drain has been added to the service area Add calculations to plan page P2.0 that derive from IPC 1003.4.2.2 showing this interceptor adequately sized.
07/27/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0523-01364
7206 N. Silverbell Rd., Bldg 4 Unit 4140 – C-1
TI – Commercial Storage (2nd Review)

TRANSMITTAL: July 27, 2023

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in C-1 Zone (UDC 4.7.20). Commercial Storage is not an allowed use in the zone, (UDC Table 4.8-4).

1. The proposed use, Automotive - Minor Service and Repair use is an allowed use in the zone subject to Use Specific Standards 4.9.4.F.2, .3, .4, & .5 and 4.9.13.O and a Zoning Examiner Special Exception Procedure, Section 3.4.3. The Special Exception must be approved prior to approval of this building plan. Special Exception requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Entitlements. Contact at Tucsonzoning@tucsonaz.gov for requirements

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/26/2023 PDSD Application Completeness REVIEW COMPLETED