Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/21/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Previous plan review comments not completely addressed.
Previous comments;

1. Please address the original plan review comments. Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code (OLC). See section 104 for plan submittal requirements.

3 See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
5 Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
6 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
9 Provide complete compliance with the 2018 IECC for the exterior lighting if applicable.
Comments this review;

Per original comment #3. Please show lighting area and option used for the lumen calculations. The lumen calculations only show the lighting area. Must also show option per table 401.1.

Per original comment #5. Lumens per acre. The site parcel for this site address 1415 N 14th AV is Parcel # 11518007F. The data per Pima County Assessor shows the parcel size as 4.8 acres, not 3.5 as shown in the lumen calculations. Please clarify. Verify that any existing exterior lighting on the site is accounted for as well as the proposed new lighting. Show this in the lumen calculations if applicable. Also show total allowed lumens and total lumens after project completion, both shielded and un-shielded.

Per original comment #6. Please indicate whether or not a special inspection is required, and needs to be shown in the lumen calculations or site lighting plans as required per section 104.2.2, 106.2.

Per comment #9. Provide compliance with the 2018 IECC for the exterior lighting power restrictions.

Questions for the Electrical plan reviewer, Email Dan Santa Cruz .... Dan.santacruz@tucsonaz.gov

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code.