| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/03/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/03/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1. The PDF format used is barely sufficient to understand the wording in the electrical drawing. Please make an effort to upgrade future plans to a legible condition. 2. It appears the loadcenter is in the bathroom. Relocate to a code compliant location. NEC 240.24(D)(E), 408.17. 3 Provide Arc Fault and GFI requirements Per NEC art 210. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||