Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/03/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.
1. The PDF format used is barely sufficient to understand the wording in the electrical drawing. Please make an effort to upgrade future plans to a legible condition.
2. It appears the loadcenter is in the bathroom. Relocate to a code compliant location. NEC 240.24(D)(E), 408.17.
3 Provide Arc Fault and GFI requirements Per NEC art 210.
Ref; 2018 IBC section 107.2.1, 2017 NEC