Permit Number: TC-COM-0523-01314
Parcel: 11207116A

Address:
2451 N TREAT AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0523-01314
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/08/2023 Commercial Mechanical REQUIRES RESUBMIT 1. The electrical service is less than 150 Amps, provide electrical load calculations.
2. The installation of an AC unit for the dwelling will require a heating/cooling load calculation to justify the capacities of the unit being installed (Sections R403.7, IECC 2018). The units themselves will also have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency and controls.
3. It appears that new gas piping will be required. Provide a gas piping layout including all loads, pipe sizes, and developed pipe lengths from the gas meter to each load.
4. Provide a structural analysis of the existing roof to determine if the new AC unit will be safely supported. Reference: Section 302.1, IMC 2018.
06/02/2023 PDSD Application Completeness Express REVIEW COMPLETED