Permit Number: TC-COM-0523-01312
Parcel: 13219102B

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0523-01312
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2023 Site Engineering APPROVED
10/27/2023 Site Zoning APPROVED
11/06/2023 Bldg Permits - Post Review REVIEW COMPLETED
10/24/2023 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Approved with Comments
Reason:
Date Completed : 6/6/2023 10:05:20 AM
1. No Geotechnical Report for the proposed buildings per International Building Code 2018, Section 1803.1 is not provided. The Inspector to verify ALL Geotechnical Information used on this Project.

2. NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/2/2023 4:46:22 PM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/23/2023 5:29:41 PM
Approved/subject to field approval



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 6/5/2023 9:06:28 AM
Electrical Review
By: Ron Ross PE
E6.0: Comment only: Lumen calculations for the two pole mounted fixtures do not appear to be calculated/on.



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 10/20/2023 4:59:07 PM
Third Plumbing Review: ok
1). resolved-Lavatory faucet on plan page P-1 needs to be automatic type Per Tucson plumbing code amendments
10/13/2023 PDSD Application Completeness REVIEW COMPLETED