Permit Number: TC-COM-0523-01297
Parcel: 10706113A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01297
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/22/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The project address per the scope of work is listed as 2920 N El Burrito per the electrical plan title block, however the electrical plan shows the proposed new Electrical Service installed on building 2880. And the information per the application details shows 2902. Please clarify.

2 Please indicate secondary conductor sizes and types on the line diagram.

Ref 2018 IBC section 107.2.1, 2017 NEC