Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0523-01295
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
01/22/2024 | Water Sterilization Report (Deferred Submittal) | REQUIRES RESUBMIT | The submitted lab results are for a different activity. | ||
01/22/2024 | PDSD Application Completeness | REVIEW COMPLETED |