Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0523-01261
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/20/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Matthew Payette mpayette@safebuilt.com Approved Reason: Date Completed : 7/18/2023 11:49:12 PM Building(B) Reviewer Matthew Payette mpayette@safebuilt.com Approved Reason: Date Completed : 6/27/2023 9:11:35 PM Mechanical(M) Reviewer Matthew Payette mpayette@safebuilt.com Approved Reason: Date Completed : 7/18/2023 11:49:38 PM No mechanical in scope. Electrical(E) Reviewer Matthew Payette mpayette@safebuilt.com Denied Reason: Date Completed : 7/18/2023 11:54:26 PM 1. According to 2017 NEC 210.8(B)(2), all receptacles in a commercial kitchen shall be GFCI protected. Revisions added note referencing 2017 NEC 406.9(A) and (B), these code articles do not require GFCI protection. |
||
| 07/13/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |