Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0523-01261
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2023 | Site Engineering | APPROVED | |||
| 06/13/2023 | Site Zoning | APPROVED | |||
| 07/03/2023 | Water - PDSD | APPROVED | |||
| 07/03/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/28/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0523-01261 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Structural(S) Reviewer Matthew Payette mpayette@safebuilt.com Denied Reason: Date Completed : 6/26/2023 8:49:59 PM No Structural plans or details provided Building(B) Reviewer Matthew Payette mpayette@safebuilt.com Approved Reason: Date Completed : 6/27/2023 9:11:35 PM Mechanical(M) Reviewer Matthew Payette mpayette@safebuilt.com Denied Reason: Date Completed : 6/26/2023 8:51:17 PM No mechanical plans or details provided. Electrical(E) Reviewer Matthew Payette mpayette@safebuilt.com Denied Reason: Date Completed : 6/26/2023 8:54:24 PM According to NEC 210.8(B)(2), all receptacles in a commercial kitchen shall be GFCI protected. This was not noted on the plans. Plumbing(P) Reviewer Matthew Payette mpayette@safebuilt.com Approved Reason: Date Completed : 6/26/2023 8:51:38 PM |
||
| 06/16/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 06/12/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |