Permit Number: TC-COM-0523-01257
Parcel: 128010190

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01257
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/22/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Ref; Electrical line diagram and Panel schedule.

1. Panel schedule for ‘H1’ shows the voltage rating at 120/208. Pleas clarify.

2. OCPD for re-fed panel ‘A’ not shown in the panel schedule ‘H1’. Please clarify.

3. Provide load calculations for panel ‘H1’ and also the total load for the ‘SES 2 of 2’.

4. Provide a grounding detail and feeder information for the 75KVA Transformer.

Ref; 2018 IBC section 107.2.1, 2017 NEC