Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0523-01257
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/22/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Ref; Electrical line diagram and Panel schedule. 1. Panel schedule for ‘H1’ shows the voltage rating at 120/208. Pleas clarify. 2. OCPD for re-fed panel ‘A’ not shown in the panel schedule ‘H1’. Please clarify. 3. Provide load calculations for panel ‘H1’ and also the total load for the ‘SES 2 of 2’. 4. Provide a grounding detail and feeder information for the 75KVA Transformer. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
07/27/2023 | PDSD Application Completeness | REVIEW COMPLETED |