Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0523-01253
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/22/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 There was no response letter located in the resubmittal as requested. It was hard for the plan reviewer to interpret the resubmitted marked up plans without a response letter addressing each comment. 2 It appears that there might have been a TYPO by the reviewer pertaining to comment # 7. The panel ‘A’ as referred to should have been Panel ‘C’. 3 Please address previous review comment # 3. Panel ‘D’ is utilizing a 3-phase circuit breaker to feed a 1 phase panel ‘B’. Revise to a 2-pole breaker or verify the 3-phase breaker is listed for use as a 2-pole breaker. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
| 06/05/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |