Permit Number: TC-COM-0523-01253
Parcel: 12905143A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0523-01253
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/22/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 There was no response letter located in the resubmittal as requested. It was hard for the plan reviewer to interpret the resubmitted marked up plans without a response letter addressing each comment.

2 It appears that there might have been a TYPO by the reviewer pertaining to comment # 7. The panel ‘A’ as referred to should have been Panel ‘C’.

3 Please address previous review comment # 3. Panel ‘D’ is utilizing a 3-phase circuit breaker to feed a 1 phase panel ‘B’. Revise to a 2-pole breaker or verify the 3-phase breaker is listed for use as a 2-pole breaker.

Ref; 2018 IBC section 107.2.1, 2017 NEC
06/05/2023 PDSD Application Completeness Express REVIEW COMPLETED