Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0523-01250
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/26/2023 | Site Zoning | NOT REQUIRED | |||
06/16/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/16/2023 | Commercial Structural | REQUIRES RESUBMIT | Please respond to the following: 1. Per IBC 1004.8 Concentrated Business use area, occupant load not less than one occupant per 50 square feet. 2. Room with 716 sf at 50 sf per occupant = 14 3. Room with 749 sf at 50 sf per occupant = 14 4. Room with 662 sf at 50 sf per occupant = 13 5. The above only increases the occupant load by 2. 6. Please resubmit. |
||
05/25/2023 | Fire New Construction | REQUIRES RESUBMIT | TC-COM-0523-01250 - 6390 E BROADWAY BL Unit: UNIT 100 – Please clarify area/scope of work. Fire alarm is required with occupant load (on second floor) over 100 (2018 IFC 907.2.2). Add deferred submittal requirement to plan set. Questions: patricia.shelton@tucsonaz.gov / 520.837.7082 | ||
05/15/2023 | PDSD Application Completeness | REVIEW COMPLETED |