Permit Number: TC-COM-0523-01250
Parcel: 134234150

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01250
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2023 Site Zoning NOT REQUIRED
06/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/16/2023 Commercial Structural REQUIRES RESUBMIT Please respond to the following:
1. Per IBC 1004.8 Concentrated Business use area, occupant load not less than one occupant per 50 square feet.
2. Room with 716 sf at 50 sf per occupant = 14
3. Room with 749 sf at 50 sf per occupant = 14
4. Room with 662 sf at 50 sf per occupant = 13
5. The above only increases the occupant load by 2.
6. Please resubmit.
05/25/2023 Fire New Construction REQUIRES RESUBMIT TC-COM-0523-01250 - 6390 E BROADWAY BL Unit: UNIT 100 – Please clarify area/scope of work. Fire alarm is required with occupant load (on second floor) over 100 (2018 IFC 907.2.2). Add deferred submittal requirement to plan set. Questions: patricia.shelton@tucsonaz.gov / 520.837.7082