Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0523-01249
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/26/2023 | Site Zoning | APPROVED | |||
06/15/2023 | Water - PDSD | APPROVED | |||
05/26/2023 | Site Engineering | NOT REQUIRED | |||
06/15/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/05/2023 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Activity Number: TC-COM-0523-01249 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Structural(S) Reviewer Daljit Benipal dbenipal@safebuilt.com Conditionally Approved Reason: Date Completed : 6/3/2023 1:37:52 PM NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/26/2023 10:55:57 AM Mechanical(M) Reviewer Neil Samaan nsamaan@safebuilt.com Denied Reason: Date Completed : 5/20/2023 11:03:59 PM 1. Provide ventilation calculations (IMC2018,403.3.1.1.1) 2. Provide gas piping riser plan, with the gas pressure at the point of delivery, and the design pressure drop, maximum gas demand and specific gravity of the fuel gas and the total pipe length from the meter to the farthest appliance. Showing all gas appliances from the meter to the furthest appliance (IFGC2018,402.3) Electrical(E) Reviewer Ron Ross rross@safebuilt.com Conditionally Approved Reason: Date Completed : 5/26/2023 2:04:06 PM Electrical Review By: Ron Ross PE E702: There are two Keyed Note #6 notes. E801B: Could not locate Keyed Note #6. Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 5/27/2023 9:06:24 PM First plumbing Review: 1). Plan page P202 needs to illustrate the sanitary & venting configurations for the service sink & break room sink -IPC 106.3.1 2). P601 fixture schedule list a bait sink & Floor sink, neither is shown on Plan page P202? -IPC 106.3.1 3). Plumbing plan pages P203 & P204 are missing from plan set but listed on plan sheet index page G001? -IPC 106.3.1 4). Include gas system sizing table calculation information within plumbing plans to show the existing system meets the demand for the new appliances -IFGC 402.4 5). Provide unit heater combustion air method with in mechanical or plumbing plans -IFGC 304 |
||
06/07/2023 | Fire New Construction | REQUIRES RESUBMIT | -Title sheet lists California Fire Code as the fire code. Tucson has adopted 2018 IFC with local amendments. Make change. -Title sheet>Miscellaneous>smokeless propellant storage. Mentions California fire code. Make change. This same section lists a letter dated May 8, 2023. Provide letter about alternate method of construction. Provide details on storage cabinets. -Sheet A601 cites IBC 1010.1.9.7 for the Von duprin locking hardware. This code section is for "I" occupancies. Delayed egress code is 1010.1.9.8. Make change. Also add appropriate sign to sheet A601, sign schedule, for the delayed egress doors per 1010.1.9.8.1 #6. -Doors with delayed egress. Coversheet lists doors 104B, 107A, 122B, 123B. Door 104B is not on the door schedule. Sheet A601 lists the doors as 103B, 107A, 122B, 123D. -Include hazardous materials management plan (HMMP) and hazardous materials inventory statement (HMIS). See IFC appendix H for requirements. john.vincent@tucsonaz.gov 5203495581 |
||
05/12/2023 | PDSD Application Completeness | REVIEW COMPLETED |