Permit Number: TC-COM-0523-01247
Parcel: 12809005H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01247
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/02/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 6/2/2023 5:02:36 PM
BUILDING INSPECTOR TO VERIFY THE GEOTECHNICAL REPORT AS STATED BELOW ON THE SITE BEFORE APPROVAL TO THE PROJECT.
1. Geotechnical Report for the proposed building per International Building Code 2018, Section 1803.1.
2. NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 8/1/2023 11:05:26 AM



Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 7/27/2023 9:48:09 PM
1. Provide detail showing how you are running your HVAC ductwork in relation to the fire rated floor/ceiling assembly sheet M2.1 (IMC2018,106.3.1) Complied
2. Provide ventilation calculations (IMC2018,403.3.1.1.1) Not Complied (MMC2018,403.3)
3. Provide mechanical ventilation to each unit sheet M1.1 (IMC2018,401.2) Not Complied same as #2
4. Bathroom exhaust in all units that penetrates the membrane of the fire rated floor/ceiling assembly shall be protected in an approved manner sheet M1.1 (IMC2018,607.6.2) Complied
5. Dryer duct that penetrates the fire rated floor/ceiling assembly in all unit's shall be protected in an approved manner sheet M1.1 (IMC2018,607.6.2) Complied




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 7/25/2023 4:17:37 PM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 7/29/2023 3:17:18 PM
Second Plumbing Review:
1). OK
2). OK
07/21/2023 PDSD Application Completeness Express REVIEW COMPLETED