Permit Number: TC-COM-0523-01240
Parcel: 13728107B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01240
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2023 Water - PDSD APPROVED -Shared Studio Session on 819-730-868 Master Permit PLANS UNDER TC-COM-0423-01167 /LEASING OFFICE, TC-COM-0523-01240/BLDG A, TC-COM-0523-01241/BLDG B, TC-COM-0523-01242/BLDG C
06/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT -Shared Studio Session on 819-730-868 Master Permit PLANS UNDER TC-COM-0423-01167 /LEASING OFFICE, TC-COM-0523-01240/BLDG A, TC-COM-0523-01241/BLDG B, TC-COM-0523-01242/BLDG C
05/31/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0423-01167 / TC-COM-0523-01240 / TC-COM-0523-01241 / TC-COM-0523-01242

GENERAL:
⦁ Provide written responses to all review comments.
⦁ Provide a complete plan set.
⦁ Provide additional documents as requested by review staff.


Structural(S) Reviewer
Daljit Benipal
dbenipal@safebuilt.com
Conditionally Approved
Reason:
Date Completed : 5/31/2023 4:51:38 PM
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/23/2023 4:35:56 PM
1. Sheet G1.02: Provide the location of egress illumination and exit lighting in accordance with Section 1008 and 1013.
2. General: Fire resistant wall/floor assemblies and penetrations typically use proprietary materials as part of the testing process for the listing. Please provide the most recently published complete listed assembly and penetration details.
3. General: Exercise equipment is required have clear floor space for access. Ensure clear floor space in accordance with Section 236.1 of the 2010 ADAAG.


Mechanical(M) Reviewer
Neil Samaan
nsamaan@safebuilt.com
Denied
Reason:
Date Completed : 5/17/2023 9:52:04 PM
1. Where bathroom, dryer, kitchen exhaust duct's and outdoor fresh air duct penetrates the fire rated floor/ceiling assembly it shall be protected in an approved manner in accordance with this section in all apartment unit's (IMC2018,607.6.2)
2. Provide ceiling radiation dampers at all ceiling supply diffuser's, provide the symbol on the plan and note it on the same page in all apartment unit's (IMC2018,607.6.2)
3. Only fire dampers and ceiling radiation dampers labeled for use in dynamic systems shall be installed in HVAC systems designed to operate with fans on during a fire event in all apartment units (IMC2018,607.3.1)
4. Provide kitchen exhaust to building D IMC2018,403.3)
5. Provide make up air for laundry room approximately equal the the total dryer exhaust rate in an approved manner (IFGC2018,614.5)


Electrical(E) Reviewer
Matthew Payette
mpayette@safebuilt.com
Denied
Reason:
Date Completed : 5/21/2023 7:37:40 PM
NEC 210.52(A)(1) requires that no point along the wall line be more than 6 feet from a receptacle outlet in dwelling units.
Provide exit signs, emergency lighting, and egress lighting in amenities building.


Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/24/2023 6:42:23 PM
First plumbing Review:
1). Roof parapet wall on plan pages A1.14, A1.24, A1.34, A1.42 needs secondary scuppers compliant with IPC 1106.5 & 1108, only primaries shown -
2). laundry room sanitary illustration on plan page P1.03 is missing the required floor drain & trap primer as shown on plan page A1.40 -IPC 413.4
3). add a note to the apartment fixture schedules on plan page P5.00 to match note#6 from building D fixture schedule same page - IPC 303.3, 402
4). Plan set submittal needs to be accompanied by the civil site utility piping plan for the continuation & correlation of the water, storm & sewer. -IPC 106.3.1
5). Add the DFU total load notation next to the Building drain exits on plan pages -P1.00, P1.01, P1.02, P1.03 -IPC 710
6). Add lint interceptor model number & manufacturer name to detail 208 on plan page P4.00 -IPC 303, 1, 1003.6
05/24/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
05/18/2023 Site Zoning REQUIRES RESUBMIT -Shared Studio Session on 819-730-868 Master Permit PLANS UNDER TC-COM-0423-01167 /LEASING OFFICE, TC-COM-0523-01240/BLDG A, TC-COM-0523-01241/BLDG B, TC-COM-0523-01242/BLDG C
FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0423-01167 – Leasing Office, TC-COM-0523-01240 – Bldg A, TC-COM-0523-01241 – Bldg B & TC-COM-0523-01242 – Bldg C
8411 S. Houghton Rd – R-2
Multifamily (1st Review)

TRANSMITTAL DATE: ‎May 18, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). Multifamily is a permitted use in the zone, (Table 4.8-2), subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

1. COMMENT: Zoning has reviewed the building plans for compliance with Development Package (DP) TD-DEV-0123-00111 and although it appears that the plans match until the DP is approved by all review agencies Zoning cannot approve the building plans.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/13/2023 Fire New Construction REVIEW COMPLETED -Shared Studio Session on 819-730-868 Master Permit PLANS UNDER TC-COM-0423-01167 /LEASING OFFICE, TC-COM-0523-01240/BLDG A, TC-COM-0523-01241/BLDG B, TC-COM-0523-01242/BLDG C
05/09/2023 PDSD Application Completeness Express REVIEW COMPLETED -Shared Studio Session on 819-730-868 Master Permit PLANS UNDER TC-COM-0423-01167 /LEASING OFFICE, TC-COM-0523-01240/BLDG A, TC-COM-0523-01241/BLDG B, TC-COM-0523-01242/BLDG C