Permit Number: TC-COM-0523-01238
Parcel: 132131240

Address:
3470 S KINO PW

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01238
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/13/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0523-01238

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/19/2023 5:54:16 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 7/10/2023 10:16:40 AM

Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/10/2023 10:19:18 AM
1. General: Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance. NOT COMPLIED

Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 7/10/2023 10:17:06 AM
1. Sheet E1.01: The electrical plans do not indicate the location of egress illumination. Provide the location of all egress illumination in accordance with Section 1008. NOT COMPLIED

Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/19/2023 5:54:10 PM
07/07/2023 PDSD Application Completeness REVIEW COMPLETED