Permit Number: TC-COM-0523-01238
Parcel: 132131240

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01238
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/25/2023 Site Zoning APPROVED
06/15/2023 Water - PDSD APPROVED
05/26/2023 Site Engineering NOT REQUIRED
06/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/19/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/19/2023 5:54:16 PM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2023 5:53:48 PM
1. Sheet A081: At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
2. Sheet A081: Provide clarification on the adjacent tenants to ensure proper separation.

Mechanical(M) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2023 5:54:04 PM
1. Sheet M0.05: The ventilation schedule does not include the calculations for the kitchen. Provide the ventilation calculations for the kitchen.
2. General: Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.

Electrical(E) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 5/19/2023 5:53:55 PM
1. Sheet E1.01: The electrical plans do not indicate the location of egress illumination. Provide the location of all egress illumination in accordance with Section 1008.

Plumbing(P) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/19/2023 5:54:10 PM
05/13/2023 Fire New Construction REVIEW COMPLETED
05/12/2023 PDSD Application Completeness REVIEW COMPLETED