Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0523-01213
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 09/11/2023 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0523-01213 (4646 E 2ND ST TUCSON, AZ 85711) Revision 1: Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. 1. Per the revision, the feeder size changes to 300 KCMIL @ 285 amps. Per 240.4(B) and Tap rule 240.21(B)(1)((1)-(4)). This would be 0k provided these requirements are met. a. CT Cabinet and Service entrance disconnect are within 10’ of the 400A loadcenter. b. Electrical load calculations for the 400A loadcenter is 400A or less. 2. Provide calculations and notes showing requirements a and b above are met, IBC 107.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||